In the USA, fires cause around $10 billion in property damage each year, while injuring or killing thousands of people. When a fire breaks out in a building, it can threaten occupants both directly and indirectly; occupants can be harmed even if they are not exposed to the heat:
If there is fire inside a building, it must be detected and extinguished as soon as possible. Therefore, having a fully-functional fire alarm system is of the highest importance. These installations can be enhanced with wireless capabilities, as long as they meet a series of key requirements. In New York City, requirements for all fire alarm systems are set forth by the following standards:
Low-Power Wide-Area Networks (LPWAN) are a very promising technology to deploy with fire alarm systems. The technology is not as fast as Wi-Fi, but can go across structural elements with much less attenuation; in urban settings, the range of LPWAN can exceed one mile, while Wi-Fi is weakened considerably with just a few walls.
Just like their wired counterparts, wireless fire alarm systems must be approved by the NYC Fire Department before installation. A full set of construction documents must be submitted for approval, which includes the floor plan and the location of key pieces of equipment, along with their specifications.
All fire alarm systems in New York City are required to have a supervising station that is approved by the fire commissioner and compliant with NFPA 72. The initial testing procedure is carried out according to NFPA 72, and periodic maintenance and tests should be carried out according to the NYC Fire Code.
The testing procedure for fire alarm systems that deploy low-power radio for wireless communication is the following:
In addition to the testing procedure above, NFPA 72 provides a list of special requirements for all low-power radio systems, which is summarized in the following table:
Requirements Category | Description |
Listing | Any low-power radio equipment used with fire alarm systems must be listed as suitable for that purpose. |
Power Supply |
A dry cell can be used as the only power supply of radio transmitters, but it must meet the requirements established in NFPA 13.16.2. In general, the battery should be able to power the device for at least one year, and automatic notifications must be generated when it is about to be depleted (7 days in advance) or if it experiences any type of failure. |
Alarm Signals |
Alarm signals must be transmitted automatically and repeated at intervals of 60 seconds or less. These signals must take priority over all others, and the control unit must display alarm activation in 10 seconds or less. When an alarm is triggered, it is required to latch in the ON position until it is reset manually. |
Signal Integrity |
Radio transmitters should be specifically listed as having a transmission method that is resistant to misinterpretation and interference. The system must identify system faults appropriately, without causing a false fire alarm. For example, interference must generate a trouble signal, and removal of a transmitter must be indicated as such by the control system (NFPA article 23.16.4). |
Remote Appliances | If remote appliances are used, they are also subject to requirements in terms of power supply , response time, latching and signal integrity (NFPA 23.16.5) |
Wireless Network Requirements in NFPA13
When wireless communications are deployed in fire alarm systems, they must meet all applicable standards from the Federal Communications Commission (FCC) and the National Telecommunications and Information Administration (NTIA). In addition, the following requirements apply:
NFPA 13 also establishes limits on the number of alarm boxes that can use the same radio frequency:
In the case of public emergency alarm signals, a dedicated frequency must be designated for two purposes: reporting alarm signals and system integrity signals.
LoRa stands for Long Range, and it is a wireless networking technology with three key characteristics:
LoRaWAN is the networking standard that deals with LoRa appliances, and its characteristics make it well suited for the use with wireless fire alarm systems:
When a LoRaWAN network is deployed, signals from individual sensors are gathered in a gateway and sent to a network server for processing. The network server can then relay key information to the NYC Fire Department.
The use of wireless communications with fire alarm systems greatly reduces the upfront cost, potentially eliminating thousands of feet of wiring. In addition, wireless fire alarm systems are less susceptible to the fire itself – wired installations are taken offline if the fire melts a key power circuit or communication line.
Like with any building system, it is strongly suggested that you hire the services of qualified engineering professionals before deploying a wireless fire alarm system. The requirements for these systems in NYC are very stringent, and you can avoid expensive corrections down the road by working with professionals who are familiarized with all applicable standards, especially NFPA 13.